CT/VT Scaling Calculator
CTVT Power transducer scaling
Full-scale MW/MVAr value for a Watt/VAr transducer, from its rated input and CT/VT ratios. Use the same figure for both the Watt and VAr output if they share the same CT/VT and rated input.
VT ratio
CT ratio
Output signal
VT ratio (used)100.00
CT ratio (used)200.00
Scaling factor19.053
Engineering range−19.053 to +19.053
Scaling factor = (√3 × V × VT ratio × A × CT ratio) ÷ 1,000,000.